Low Point Drains: Prevent Freeze Damage in Colorado Dry Sprinkler Systems

Fire Suppression

Stop Frozen Pipes Cold: Winterization for Low Point Drains

Why Auxiliary Drain Testing Is Critical for Every Dry Sprinkler System in Colorado


TL;DR
Dry sprinkler systems in Colorado naturally accumulate moisture, and even a small amount of trapped water can freeze and rupture piping. Low point drains must be checked and emptied regularly—or systems can fail when temperatures drop. Daily or weekly draining, plus specialty trip testing, is essential for winter readiness. If your drains haven’t been serviced this season, your system is not winter-ready.

Introduction: Winter Doesn’t Wait — Neither Should Your System

Every winter, dry sprinkler systems in Colorado freeze and fail—not because of design flaws, but because water was left trapped inside the pipe.
Even a teaspoon of water can freeze, expand by 9%, and create more than 30,000 psi of pressure—enough to split steel.
 
The single most common cause we see? Neglected Low Point Drains (aka Auxiliary Drains). If these drains aren’t checked and emptied regularly, your dry system can quickly become a freeze-and-flood emergency.

1. “Dry” Systems Are Never Truly Dry — The Condensation Problem

Dry pipe sprinkler systems are installed in cold areas—garages, attics, loading docks, exterior canopies—where temperatures cannot reliably stay above 40°F. These systems use pressurized air or nitrogen instead of water.
But “dry system” is a misleading term.

Three reasons dry systems still accumulate water:

  1. Condensation from Humid Air (Compressor Intake)
  2. Compressors draw in outside air that contains moisture. Inside cold steel piping, that moisture condenses into liquid water.
  3. Residual Water From Hydrostatic Testing
  4. After installation or repairs, systems undergo hydrostatic testing. Complete drainage is impossible—small pockets of water always remain.
  5. Colorado’s “Polar Coaster” Temperature Swings
  6. Warm days followed by sub-zero nights create constant vapor cycling and condensation inside pipe networks.
 
Result: Water always settles in the lowest points unless manually drained.

2. What Is a Low Point Drain (Auxiliary Drain)?

Low Point Drains—also called auxiliary drains—are required by NFPA 13 at the lowest elevations of a dry sprinkler system. Their purpose is to collect and safely discharge trapped water before it freezes.

Important distinction:

  • All drum drips are low point drains.
  • Not all low point drains are drum drips.
A drum drip is the most common LPD configuration—a two-valve assembly designed for controlled drainage without releasing system air pressure.
 
Low point drains are typically located in:
  • Parking garages
  • Attic spaces
  • Exterior canopies
  • Vestibules and entryways
  • Mechanical huts
  • Any area with dips, slope changes, or long horizontal runs
 
These drains are not optional accessories—they are essential freeze-prevention components.

📢 Fire & Life Safety Decoded Fact:

NFPA 25 places the responsibility for inspection on the owner, but the execution of repairs or complex testing requires a licensed professional.

3. How Low Point Drain Testing Works

During testing and maintenance, a technician confirms:
  • Presence of water — indicates condensation load or drainage failure.
  • Valve condition — stiff, seized, or leaking valves increase freeze risk.
  • Flow rate during draining — slow flow may indicate deeper pockets of water.
  • Proper pipe pitch — incorrect slope traps water upstream.
  • Evidence of previous freezing — rust staining, cracked fittings, paint bubbles.
  • Correct drainage sequence — critical for avoiding accidental system trips.

⚠️ Critical Warning

If both valves on a drum drip are opened simultaneously:
  • System air pressure can vent rapidly.
  • The dry valve may accidentally trip.
  • Water may flood into exposed, freezing-cold piping.
 

This is one of the most common—and preventable—winter failures.


4. How Often Should Low Point Drains Be Emptied? (NFPA 25)

NFPA 25 Section 13.4.5.3.2 requires LPDs be emptied:
  • After every system operation
  • Before freezing weather
  • And “as needed” throughout winter

The Colorado Reality

  • Daily draining during extended freezing periods
  • Weekly draining during fall and spring fluctuations
  • More frequent draining in high-humidity areas such as:
    • Vestibules and entryways
    • Parking garages
    • Mechanical huts
  • Professional winterization before the season’s first hard freeze
Failing to follow these intervals is the #1 cause of dry system freeze-ups.
 
🔸 Liability Tip: The “Look, Don’t Touch” Rule Many property managers ask: “Can my maintenance guy just fix the broken valve?”
The answer is No. While NFPA 25 assigns the responsibility of inspection to the owner, the execution of repairs or complex testing must be done by a qualified professional.
 
Attempting DIY repairs on a pressurized system is dangerous and illegal without the proper license.

5. Entryways: The Hidden Freeze Trap

Entryways, vestibules, enclosed entrances, semi-conditioned entrances, and other unheated transition zones are among the highest-risk locations for freeze damage.

Why these areas freeze first:

  • Warm interior air meets freezing exterior air.
  • Door cycles pull cold drafts directly across piping.
  • Shallow ceiling spaces lose heat rapidly.
  • Exposed overhead low points allow water to pool.
  • Rapid swings in temperature accelerate condensation.
 
A freeze in these areas can:
  • Burst elbows or fittings
  • Flood primary building entrances
  • Create overhead electrical hazards
  • Block tenant and customer access
  • Result in costly downtime and repairs
 
These failures are extremely common—and completely preventable.

6. The Physics of Ice Expansion — What Actually Breaks Pipes

When water freezes:
  • Volume increases by ~9%
  • Pressure rises above 30,000 psi
  • Steel and cast-iron fittings split open

 

The “Ice Plug” Effect
When a pipe ruptures during a freeze, the ice often seals the break—meaning:
  • Damage is hidden
  • Leaks appear only when temperatures rise
  • Systems may fail when they attempt to recharge or activate
 
This is why freeze damage is often discovered after a cold snap.
 

7. Don’t Gamble with Your Dry System — Winterize Now

Low Point Drain testing protects:
  • Life and property
  • Building infrastructure
  • System reliability
  • Insurance compliance

The professionalism and care shown by everybody my team and I interact with is outstanding. They are always quick to respond, very on top of regular scheduling, and immensely informative with my team, allowing us to maintain our equipment and keep everyone in the loop.

Michael Quinealty

Love this team!! Positive Responsiveness, Quality, Professionalism

Mellisa McBryde

Awesome experience overall. Showed up on time and took care of everything. Will do business with them in the future.

Peter Ferraro
Integrity Fire Colorado Skyline